Fuse data (F1 ... F3)
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Cable installaon in accordance
with
NFPA 70, NFPA 79
Fuse
Standard UL 248
Typ. Rated current A 3 6
Max. rated current A 3 10
Semiconductor fuse
Standard UL 248
Typ. Rated current A 3 6
Max. rated current A 3 10
Circuit breaker
Standard UL 489
Typ. Rated current A 15 15
Max. rated current A 15 15
WARNING!
UL marking
Suitable for use on a circuit capable of delivering not more than 5k rms symmetrical
amperes, 480 V maximum.
When protected by fuses rated, see table above.
When protected by a circuit breaker having an interrupng rang not less than 5k rms
symmetrical amperes, 480 Maximum, see table above.
Marquage UL
Convient à une ulisaon sur un circuit non suscepble de délivrer plus de 5k ampères
symétriques e, maximum 480 V.
Avec une protecon par des fusibles du calibre indiqué dans le tableau ci-dessous,
Avec une protecon par un disjoncteur à courant de coupure assigné d’au moins
5k ampères symétriques e, maximum 480 V, voir tableau ci-dessous.
Group drive connecon according to NFPA 70, NFPA 79
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
Informaon on electrical installaon
Connecon according to cULus
45