Environmental condions
Climate
Storage EN 60721-3-1:1997
1K3 (-30 ... +60°C) <3 months
1K3 (-30 ... +40 °C) >3 months
Transport EN 60721-3-2:1997 2K3 (-30 ...+70 °C)
Operaon
EN 60721-3-3:1995 +
A2:1997
3K3 (-30 ...+40 °C) Operaon
Site altude
0 … 1000 m amsl
-
Without current derang
1000 … 4000 m amsl Reduce rated output current by 5 %/1000 m
Polluon
- EN IEC 61800-5-1 Degree of polluon 2
Vibraon resistance
Operaon
EN 60721-3-3:1995 +
A2:1997
3M4
Transport EN 60721-3-2:1997 2M2
Vibraon severity
A EN IEC 60034-14 - -
Electrical supply condions
Possibility of connecon to dierent types of mains power supply enables worldwide use.
The following is supported:
•
3-phase mains connecon 400 V
•
3-phase mains connecon 480 V
Type of mains power supply
TT Mains power supplies with earthed start point
Voltage against earth: max. 300 V
TN
Technical data
Standards and operang condions
Environmental condions