EasyManua.ls Logo

Lenze Global Drive 8200 motec Series

Lenze Global Drive 8200 motec Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter setting
Parameter setting using the keypad
7
l EDK82MVXXX EN 1.0
2.1.2 The menu U
UU
Us
ss
se
ee
er
rr
r - The 10 most important drive parameters
After mains switching or plugging in the keypad during operation, the 10 codes defined to be the
most important in the user menu User (Code C0517) are available immediately.
In default setting the menu contains User all codes required for a standard application with linear V/f
characteristic control.
Code Name Lenze setting
C0050 Output frequency Display: Output frequency without slip compensation
C0034 Setpoint selection range -0-
Standard I/O X3/8: 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
0
0
3
4
S
e
t
p
o
i
n
t
s
e
l
e
c
t
i
o
n
r
a
n
g
e
0
Application I/O
X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V
C0007 Fixed configuration of digital inputs -0-
E4 E3 E2 E1
0
0
0
7
F
i
x
e
d
c
o
n
f
i
g
u
r
a
t
i
o
n
o
f
d
i
g
i
t
a
l
i
n
p
u
t
s
0
CW/CCW DCB JOG2/3 JOG1/3
CW/CCW rotation DC-injection brake
Selection of fixed setpoints
C0010 Minimum output frequency 0.00 Hz
C0011 Maximum output frequency 50.00 Hz
C0012 Acceleration time main setpoint 5.00 sec
C0013 Deceleration time main setpoint 5.00 sec
C0015 V/f rated frequency 50.00 Hz
C0016 U
min
boost depending on the inverter type
C0002 Parameter set transfer/reset seecodetable
Tip!
Use C0002 Parameter set transfer to easily transfer configurations from one controller to the other
or to reset the controller to Lenze settings.
efesotomasyon.com - Lenze