Troubleshooting an d fault elimination
Maloperation of the drive
9
l EDK82MVXXX EN 1.0
3 Troubleshooting and fault elimination
3.1 Maloperation of the drive
Fault Cause Remedy
Motor d oes not
rotate
DC-bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display
LU)
Check mains voltage
Controller inhibited
(Green LED is blinking, keypa d display:
c)
Remove the controller inhibit, controller inhibit can be set
through several sources
Automatic start inhibited (C0142 = 0 or 2) LOW-HIGH edge at X3/28
If necessary, correct start condition (C0142)
DC injection brake active (DCB) Deactivate DC-injection brake
Mechanical motor brake is not released Manual or electrical release of mechanical motor brake
Quick stop (QSP) active (keypad display: c ) Remove quick stop
Setpoint = 0 Setpoint select ion
JOG setpoint activated and JOG frequency = 0 JOG setpoint selection (C0037 ... C0039)
Active fault Eliminat e fault
Wrong parameter set active Change to correct parameter set via terminal
Control mode C0014 = -4- , -5-, but no motor parameter identification Motor parame ter identification (C0148)
Under C0410 several functions, which e xclude ea ch other, are a ssigned t o the
same signal source.
Correct configuration in C0410
Use internal voltage source X3/20 for function modules Standard-I/O, INTERBUS,
PROFIBUS-DP or LECOM-B (RS485):
Bridge between X3/7 and X3/39 is missing
Jumper terminals
Motor d oes not
Defect ive motor cable Check motor cable
M
o
t
o
r
d
o
e
s
n
o
t
rotate smoothly
Maximum current too low (C0022, C0023) Adaptation to application
r
o
t
a
t
e
s
m
o
o
t
h
l
y
Motor underexcited or overexcited Check parameter setting (C0015, C0016, C0014)
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not adapted to
the motor data
Manual adaptation or identification of motor parameters
(C0148)
Current
Setting of C0016 t oo high Correct setting
C
u
r
r
e
n
t
consumption of
Sett ing of C0015 too low Correct setting
c
o
n
s
u
m
p
t
i
o
n
o
f
motor too high
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not adapted to
the motor data
Manual adaptation or identification of motor parameters
(C0148)
Motor rotates,
setpoints are
ā€œ0ā€
With the function j of the keypad a setpoint has been selected. Set the setpoint to ā€0ā€ by C0140 = 0
Motor
parameter
i
d
e
n
t
i
f
i
c
a
t
i
o
n
Motor too small compared with rated power
i
d
en
t
i
f
i
ca
t
i
on
stops with error
LP1
DC brake active via terminal
Unacceptable
drive response
with vector
control
various Vector control optimisation