Wiring the device modules
Communication modules
8
68
EDK94AMH24 DE/EN/FR/ES/IT 1.0
DIP switch
Pos. Description
Addressing of the bus node
Baud
CAN Address
O
N
cdba
64
32
16 8
421
9400CAN003
Fig.16-3 Arrangement and labelling of t he DIP switches
On memory modules with front-panel DIP switches you can set
ƒ the node address (labelling ”1” ... ”64”) and
ƒ the baud rate (labelling ”a” ... ”d”).
Note!
If all address switches are in the ”OFF” position when the standard device is
switched on, the configurations stored under codes C00350 (node address)
and C00351 (baud rate) are valid.
Switch off the voltage supply of the standard device and then switch it on
again to activated changed settings.
Setting of the node address
The node address of the drive results from the sum of all address switches in ON position.
Setting of the baud rate
d c b a Baud rate
OFF ON ON OFF 10 kbps
OFF ON OFF ON 20 kbps
OFF OFF ON ON 50 kbps
OFF OFF ON OFF 125 kbps
OFF OFF OFF ON 250 kbps
OFF OFF OFF OFF 500 kbps
ON ON ON OFF 800 kbps
OFF ON OFF OFF 1000 kbps
OFF ON ON ON Autobaud
Displays
Pos. Colour Condition Description
MS Green On Communication module is supplied with voltage.
DE Red On Communication module is not accepted by the standard device
(see notes given in the documentation for the standard device).
BS Green
Signalling according
to DR303-3
CANopen state (”Z”)
BE Red CANopen error (”F”)