Inverter i550-C30/400-3 i550-C37/400-3 i550-C45/400-3 i550-C55/400-3
Rated power kW P
N
37 45 55 75
Rated power hp P
N
50 60 75 100
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
without mains choke A I
r, AC
- - - -
with mains choke A I
r, AC
59 73 86 105
Apparent output power kVA A
ON
49 61 72 89
Rated output current
2 kHz A I
OUT
62.4 78 92.4 115
4 kHz A I
OUT
62.4 78 92.4 115
8 kHz A I
OUT
- - - -
16 kHz A I
OUT
- - - -
Power loss
2 kHz W 761 942 1101 1358
4 kHz W 810 1004 1171 1446
8 kHz W - - - -
16 kHz W - - - -
at inverter disablecontroller
inhibit
W 25 25 25 30
Overcurrent cycle 180 s
Max. output current A I
max, out
78 98 116 144
Overload me s t
ol
60 60 60 60
Recovery me s t
re
120 120 120 120
Max. output current during the
recovery me
A 39 49 58 72
Overcurrent cycle 15 s
Max. output current A I
max, out
104 130 154 192
Overload me s t
ol
3 3 3 3
Recovery me s t
re
12 12 12 12
Max. output current during the
recovery me
A 39 49 58 72
Cyclic mains switching 3 mes per minute 1 me per minute
Brake chopper
Max. output current A I
max, 1
98 98 98 166
Min. brake resistance Ω R
min
7.5 7.5 7.5 4.7
Max. motor cable length shielded
without EMC category m 100 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 35 35 100
Weight kg 17.2 17.2 17.2 24
Weight lb 38 38 38 53
Technical data
3-phase mains connecon 480 V "Light Duty"
Rated data
185