Informaon on electrical installaon
Important notes
DANGER!
Electrical voltage
Possible consequences: Death or severe injuries
Any work on the inverter must only be carried out in the deenergised state.
Inverter up to 45 kW: Aer switching o the mains voltage, wait for at least 180 s before
you start working.
Inverter from 55 kW onwards: Aer switching o the mains voltage, wait for at least 600 s
before you start working.
DANGER!
Dangerous electrical voltage
The leakage current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an
error.
Implement the measures requested in EN 61800−5−1 or EN 60204−1. Especially:
Fixed installaon
The PE connecon must comply with the standards (PE conductor diameter ≥ 10 mm
2
or
use a double PE conductor)
NOTICE
No protecon against excessively high mains voltage
The mains input is not fused internally.
Possible consequences: Destrucon of the product in the event of excessively high mains volt-
age.
Take note of the maximum permissible mains voltage.
On the mains supply side, use fuses to adequately protect the product against mains uctu-
aons and voltage peaks.
DANGER!
Use of the inverter on a phase earthed mains with a rated mains voltage ≥ 400 V
The protecon against accidental contact is not ensured without external measures.
If protecon against accidental contact according to EN 61800-5-1 is required for the control
terminals of the inverters and the connecons of the plugged device modules, ...
an addional basic insulaon has to be provided.
the components to be connected have to come with a second basic insulaon.