Loading...
Fusing data
Inverter i550-C1.1/230-1 i550-C1.1/230-2 i550-C1.5/230-1 i550-C1.5/230-2
Cable installaon in compliance
with
EN 60204-1
without mains choke
Circuit breaker
Characteriscs B
Max. rated current A 25 25 25 25
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25 25 25
with mains choke
Circuit breaker
Characteriscs B
Max. rated current A 25 25 25 25
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
Fusing data
Inverter i550-C2.2/230-1 i550-C2.2/230-2
Cable installaon in compliance
with
EN 60204-1
without mains choke
Circuit breaker
Characteriscs B
Max. rated current A 25 25
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
with mains choke
Circuit breaker
Characteriscs B
Max. rated current A 25 25
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B