Commissioning
Operang Instrucons i550-Cabinet
Display code Designaon Possiblesengs/valueranges Keypad code Informaon
P323.00 Motor current
0.001 ... 1.700 ... 500.000 A *
Seng of the rated motor current according to motor nameplate.
P324.00 Max current 0.0 ... 200.0 ... 3000.0 % Maximum overload current of the inverter.
P400.01 Inverter enable TRUE [1] Assignment of a trigger to the “inverter enable“ funcon.
Trigger = TRUE: The inverter is enabled (unless there is another cause for inverter disable).
Trigger = FALSE: The inverter is disabled. The motor has no torque and coasts.
P400.02 Run Digital input 1 [11] Assignment of a trigger to the “Run” funcon.
Funcon1:Start/stopmotor(defaultseng)
Funcon 1 is acve if no further start commands (start forward/start reverse) have been connected to triggers, no keypad control is acve and
no network control is acve.
Trigger = TRUE Let motor rotate forward (CW).
Trigger = FALSE: Stop motor according to stop funcon (P203.03).
Funcon2:Startenable/stopmotor
Funcon 2
is acve if further start commands have been connected to triggers, the keypad control is acve or the network control is acve.
Trigger = TRUE: Start commands of the acve control source are enabled.
Trigger = FALSE: Stop motor.
P400.03 Quick stop Not connected [0] Assignment of a trigger to the “Acvate quick stop” funcon.
Trigger = TRUE: Acvate quick stop. Quick stop ramp P225.00.
Trigger = FALSE: Deacvate quick stop
P400.04 Error reset Digital input 2 [12] Assignment of a trigger to the “Reset error” funcon.
Trigger = FALSE >
TRUE (edge): Acve error is reset (acknowledged) if the error condion is not acve anymore and the error is reseable.
Trigger = FALSE: No acon.
P400.05 DC braking Not connected [0] Assignment of a trigger to the “Acvate DC braking” funcon.
Trigger = TRUE: Acvate DC braking.
Trigger = FALSE: Deacvate DC braking.
P400.06 Start forward Not connected [0] Assignment of a trigger to the “Start forward (CW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate forward.
Trigger = TRUE > FALSE (edge): No acon.
Stop via P400.01 (default seng of digital input 1).
P400.07 Start reverse Not connected [0] Assignment of a trigger to the “Start reverse (CCW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate backward.
Trigger = TRUE > FALSE (edge): No acon.
Stop via P400.01 (default seng of digital input 1).
P400.08 Run forward Not connected [0] Assignment of a trigger to the “Run forward (CW)” funcon.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default seng of digital input 1).
P400.09 Run reverse Not connected [0] Assignment of a trigger to the “Run reverse (CCW)” funcon.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default seng of digital input 1).
P400.13 Reverse rot. dir. Digital input 3 [13] Assignment of a trigger to the “Reverse rotang direcon” funcon.
Trigger = TRUE: The setpoint specied is inverted (i.e. the sign is inverted).
Trigger = FALSE: No acon / deacvate funcon again.