29
Troubleshoong
Operang Instrucons i550-Cabinet
Error code Descripon Classicaon Remedy
Blocking
me[s]
Reset
possible
5112
24 V supply fault Warning • Check oponal external 24V voltage supply (terminal X3/24E), if connected.
• Check mains voltage.
0 Yes
5180
24-V supply overload Warning • Check 24-V output and digital outputs for earth fault or overload. 0 Yes
6280
Trigger/funcons connected incorrectly Trouble • Check and correct the assignment of the triggers to the funcons.
• With keypad or network control, the two funcons “Inverter enable” (P400.01) and “Run” (P400.02) can also be set to
“Constant TRUE [1]” to start the motor.
0 Yes
7180
Motor overcurrent Fault • Check motor load. • Check drive sizing.
• Adapt the set error threshold (P353.01).
1 Yes
9080
Keypad removed Fault • Plug on the keypad again or acvate another control source. 0 Yes
FF02
Error: Brake resistor overload Fault • Check drive sizing.
• Check sengs for the braking energy management.
Note: The error will be reset if the thermal load falls below the error threshold (P707.09) of - 20 %.
5 Yes
FF06
Motor overspeed Fault • Adapt the maximum motor speed (P322.00) and the error threshold (P350.01). 1 Yes
FF36
Warning: Brake resistor overload Warning • Check drive sizing.
• Check sengs for the braking energy management.
Note: The warning will be reset if the thermal load falls below the warning threshold (P707.08) of - 20 %.
0 Yes
FF37
Automac start disabled Fault • Deacvate start command and reset error. 0 Yes
FF85
Keypad full control acve Warning
• To exit the control mode, press the
keypad key.
0 Yes