Operating instructions i550 cabinet frequency inverter | 40
© 11/2021 · EN · www.Lenze.com
Display code Name Possible settings Keypad code Information
P225.00 QSP del.time 1.0s
Quick stop deceleration time for “MS: Velocity mode”
• If the "Quick stop" function is activated, the motor is brought to a standstill within the deceleration time set here.
• The braking deceleration time set refers to the deceleration from the maximum frequency set (P211.00) to standstill. In
the case of a lower actual frequency, the actual deceleration time is reduced accordingly.
• Setting is not eective in the operating mode P301.00 = “CiA: Velocity mode [2]”.
Basic setting (group 2)
Commissioning
Parameter overviewTerminal controlKeypad controlImportant notesInitial switch-on
Extended
terminal control
Keypad module
Additional functions
Basic setting Motor control
Favorites