Display code Name Possible settings Keypad code Information
P320.04 Rated torque 50 ... 50000 rpm
General motor data.
Carry out settings as specied by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase connection implemented for the motor (star or
delta connection).
Only enter the data applying to the connection type selected.
P320.05 Rated frequency 1.0 ... 10000.0Hz
P320.06 Rated power
0.00 ... 655.35 kW
0.00 ... 878.84 hp
P320.07 Rated voltage 0 ... 65535V
P320.08 Cos phi 0.00 ... 1.00
P327.04 Mot. identif. 0 ... 1
1 = start automatic identication of the motor data.
Inverter characteristics, motor equivalent circuit diagram data and controller settings are identied and set
automatically.
During the procedure, the motor is energized!
P327.05 Mot. calibrate 0 ... 1
1 = start automatic calibration of the motor data.
A default inverter characteristic is loaded.
The motor equivalent circuit diagram data and controller settings are calculated on the basis of the currently set rated
motor data.
The motor is not energized.
Motor control (group 3)
Commissioning
Parameter overviewTerminal controlKeypad controlImportant notesInitial switch-on
Extended
terminal control
Keypad module
Additional functions
Basic setting Motor control
Favorites

Related product manuals