Electrical
installaon
Important notes
DANGER!
Dangerous electrical voltage
The pr
oduct's power connecons can sll be carrying voltage when the mains supply has been
switched o.
Possible consequences: Death or severe injuries when touching the power terminals.
Do not touch the power connecons immediately. Take note of the corresponding warning
plates on the product.
Check to make sure that all power connecons are deenergised.
DANGER!
Dangerous electrical voltage
The leak
age current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an
error.
Implement the measures required in EN 61800-5-1, especially:
Fixed installaon
The PE connecon must comply with the standards (PE conductor diameter ≥ 10 mm
2
or
use a double PE conductor)
NOTICE
No
protecon against excessively high mains voltage
The mains input is not fused internally.
Possible consequences: Destrucon of the product in the event of excessively high mains volt-
age.
Take note of the maximum permissible mains voltage.
On the mains supply side, use fuses to adequately protect the product against mains uctu-
aons and voltage peaks.
Mounng/
installaon
Electrical installaon
Important notes
58