THERMA V Monobloc
7. Capacity Tables
22
Product Data
FHBW126B0 [HM121HF UB60], FHBW128B0 [HM123HF UB60]
Note
1. DB : Dry bulb temperature(℃), LWT : Leaving water temperature(℃), LPM : Liter per minute ( ℓ /min)
2. TC : Total capacity(kW), EER: Energy efficiency ratio(kW/kW), COP : Coefficient of performance (kW/kW)
3. Direct interpolation is permissible. Do not extrapolate.
4. Measuring procedure follows EN14511.
• Rated values are based on standard conditions, and it can be found on specifications.
• Above table values may not be matched according to installation condition. Except for rated value, the performance is not guaranteed.
• In accordance with the test standard(or nations), the results may vary.
5. The Shaded areas are not guaranteed continuous operation.
Outdoor
Temperatu re
[°C DB]
Water flow rate 33.1 LPM
LWT 7 °C LWT 10 °C LWT 13 °C LWT 15 °C LWT 18 °C LWT 20 °C LWT 22 °C
TC EER TC EER TC EER TC EER TC EER TC EER TC EER
20 11.50 4.02 11.50 4.35 11.50 4.69 11.50 4.92 11.50 5.27 11.50 5.50 11.50 5.74
30 10.97 3.41 11.50 3.79 11.50 4.09 11.50 4.33 11.50 4.56 11.50 4.68 11.50 4.64
35 10.50 3.12 11.28 3.33 11.50 3.53 11.50 3.74 11.50 3.78 11.50 4.02 11.50 4.09
40 9.35 2.74 10.08 2.91 10.80 3.07 11.27 3.22 11.50 3.36 11.50 3.45 11.50 3.54
45 8.19 2.34 8.90 2.49 9.61 2.62 10.07 2.70 10.77 2.82 11.23 2.90 11.50 2.99