-14-
2. Protection of the evaporator pipe from frosting
If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode,
compressor, outdoor fan are turned off.
When indoor pipe temp. is 7°C or higher after 2 min pause of compressor
compressor, outdoor fan is turned on according to the condition of the room temperature.
3. Protection of the indoor fan from droplet formation (Enclosure
sweat and condensed disposal test)
• Control condition : The system operates standard operation without this condition as follows.
- Setting temperature <25°C
- Indoor fan speed low speed
- Outdoor temperature < 31°C
• Control method
- Operation frequency of compressor must be below (refer to the comp. Freq. table)
- The indoor fan operates at medium speed.