LG LS-K1860YL - Cooling Mode Operation

LG LS-K1860YL
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-15-
4. Cooling mode operation
Operating frequency of compressor depend on the difference of the temperature.
(= intake air Temp.- Compressor off Temp.
Compressor off temp.= setting temp.
-
0.5°C
on temp. = setting temp. +0.5°C
If compressor operates at some operating frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp.
-
0.5°C and setting temp.
-
1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp.
-
1.0°C.
Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences
over 2.5°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 12
Step 10
Step 8
Step 4
Step 2
Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
7K Btu Series
9K Btu Series
12K Btu Series
18K Btu Series
Comp. Operating frequency
40 47 54 64 74 85
45 53 72 86 95 110
35 47 51 58 62 67
35 47 57 66 71 96
Step 1 Step 2 Step 4 Step 8
(Fc)
Step 10 Step 12