-17-
6. Heating mode operation
Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 26°C
off: indoor pipe temp. < 37°C
While in defrost control, between the indoor and outdoor fans are turned off.
Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 19
Step 15
Step 13
Step 9
Step 5
Step 3
Step 1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Model
7K Btu Series
9K Btu Series
12K Btu Series
18K Btu Series
Comp. Operating frequency
42 47 56 67 80 86 90
42 56 68 82 95 103 110
41 49 57 64 72 76 83
41 47 53 58 67 71 76
Step 1 Step 3 Step 5 Step 9
Step 13(Fh)
Step 15 Step 19