Single Zone Vertical Air Handling Unit - CV Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Installing Ductwork
Installing Ductwork
Install ductwork to the 4-way Vertical Air Handling Unit as required for
your system. Some general guidelines are:
Use more than 10 screws to join the supply duct to the VAHU.
Seal all duct work according to local codes to prevent air leakage.
Ensure that filter access is unobstructed.
The VAHU support platform must be sturdy enough to support the
cabinet plus any accessory components including filter box.
The minimum height clearance is 14 inches to maintain proper air flow.
Vibration isolators (field supplied) must be placed between the unit
and the pedestal.
To prevent vibration transmission, use flexible connectors between
duct and the unit. If the optional electric heater is installed, it is man-
datory that the flexible connector between unit and duct at discharge
connection is made of heat resistant material.
Duct work must be insulated and covered with vapor barrier when
routed through unconditioned space.
To prevent the formation of condensation, insulate the duct well.
Internal acoustical insulation lining may be necessary for the metal
duct system if it does not have a 90° elbow and 10ft. of main duct to
the first branch takeoff.
It is advised that a fibrous duct work could be used as a substitute
if built and installed in accordance with the most recent edition of
SMACNA construction standard on fibrous glass ducts.
Collectively, fibrous duct work and acoustical lining must follow Na-
tional Fire Protection Association standards 90A or B as tested by UL
standard 181 for class 1 air ducts.
Seal around the duct after it is secured to prevent air leaks.
More than 6 screws (M4*25L)
More than
1inch (25mm)
Field Supplied
Return Plenum
Field Supplied
Supply Duct
Do not connect screws on front and rear side;
they may interfere with filter installation.
More than 10 screws
(M4*25L)
Figure 27: Installing Ductwork.
Figure 28: Securely Fasten Supply Duct.
GENERAL INSTALLATION GUIDELINES