Operation Details
n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).
• The operation diagram is as following.
ON
ON
Off Off LowLow
1 min
Hotstart On
Hotstart Off
Indoor unit
Heat-Exchanger
temperature
Setting fan
speed
Setting fan
speed
Thermal
Outdoor fan
Indoor fan
4way Valve
ON
1 min
• Initial Hotstart On state
¿ Power Off On
¡ Operation Off On
¬ Cooling operation Heating operation
Defrost operation