EasyManuals Logo

LG Multi V ARUB Series User Manual

LG Multi V ARUB Series
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
96 Outdoor Unit
Test Run
Sensor Checking Function
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or
not. 3 indoor temperature sensors, 10 outdoor temperature sensor
Note 1)
, 2 outdoor pressure sensors.
This function is used along with Refrigerant Auto recharge and Quantity auto decide function.
It is used for judging sensor abnormality.
Note2)
DIP Switch Settings
Warning : Please reset SUB PCB before starting this function
- Setting1
(Refrigerant Auto Recharge)
- Setting2
(Refrigerant Quantity Auto Decide)
- Setting3
(Integrated Test Run - cooling)
- Setting4
(Integrated Test Run - heating)