EasyManua.ls Logo

LG multi V ARUM Series - MODBUS Communication; Modules Wiring Diagram While Using MODBUS Protocol (Fig. 6)

LG multi V ARUM Series
19 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2020/07/23 page 13
5.4 CONTROL / COMMUNICATION MODBUS
In order to control up to 23 modules from the
superior system you may use the MODBUS
communication as an option to control or monitor the
equipment.
Input/output “MODBUS“ (terminals 23+24)
The address for MODBUS communication is set using
the “SETTINGS” button. The setting procedure to be
found in paragraph 6.
PARAMETRY KOMUNIKACE MODBUS
Serial line: 9.6 kbps, 8 bits, no parity, 1 stop bit
Station address: hex91 - hexA7 (default hex91)
Supported functions: - 3 (Multi_Read)
- 6 (Single_Write)
- 16 (Multi_Write)
Fig.6 - MODBUS communication wiring diagram
for controlling multiple modules
READING REGISTRIES
Name
Address
(decadically)
Properties/description
VERSION
4096
Software version
ERROR
4097
Errors according to the device’s self-diagnostics (see the service manual of the
LG device), (error 99 + Modbus communication error)
TEMP1
4098
Refrigerant input temperature to the exchanger +15 °C (blue sensor, smaller
diameter)
TEMP2
4099
Refrigerant output temperature to the exchanger +15 °C (red sensor, bigger
diameter)
DEFROST
4100
1 = active defrost mode of the outdoor unit
RECORDING REGISTRIES
Name
Address
(decadically)
Properties/description
POWER
4101
The value of the required power 0 to 7 corresponds with analogue input
FUNCTION
4102
Bit 0
0 = cooling; 1 = heating (heat pump)
Bit 1+2
Power value 0,1,2,3 (this value is used to control the power only if the
value in the registry POWER is = 0)
Bit 3
0 = OFF; 1 = ON
Bit 6
1 = RESET
I&C

Related product manuals