EasyManua.ls Logo

LG multi V ARUM Series - Control Diagram - Power Request for Analogue Input (Fig. 4); Logic Input Control Diagram (Fig. 5)

LG multi V ARUM Series
19 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2020/07/23 page 11
“POWER LEVEL REQUEST”
Fig.4 - Control diagram Power request for analogue input (Operational mode through logic input)
A request for power level may be
executed through an analogue signal
0…10VDC or through 3 logic inputs
(voltage free contacts).
To directly influence the output
(change of evaporating temperature in
cooling mode/change of condensing
temperature in heat pump mode) it is
necessary to install a capacity
limitation module at the same time.
1. Input terminals POWER 0…10V“
(terminals 16+17) analogue
signal 0…10V (0 V = no request
for power level, 10 V = maximum
power level request). The current
power request is shown on the
right side of the display module
using 8 codes (“C0…C7“ or rather
“H0…H7“).
The power request algorithm requires
at least "C1"/"H1" code (i.e. at least
1.5V) to activate the compressor unit.
The power request algorithm requires at least "C0"/"H0" code (that means maximum 1.3V) to stop the
compressor unit.
Fig.5 - Logic input control diagram free contact type
2. Input terminals “POWER
1ST,2ST,3ST“ logic inputs
(voltage free contacts):
no contact closed = no
power request
contact POWER 1st closed
(terminals 18+20) = low
power request
contact POWER 2st closed
(terminals 18+21) = higher
power request
both contacts POWER
1ST+2ST closed (terminals
18+20+21) = maximum
power request
the current power demand is
displayed on the right position
of the module display via 4
codes (“C0, C1, C3, C7, or
“H0, H1, H3, H7”)
Power control
Level 1 to 7
Cool / Heat
Start / Stop
I&C
Cool / Heat
Power level
0,1,4,7
Stop / Start
I&C

Related product manuals