Individual Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum
space as shown in the figures below.
Category Installation Space
Case 1
(10 mm≤Side Space≤49 mm)
Case 2
(Side Space≥49 mm)
4 sides
are walls
Only 2
sides are
walls
Limita-
tions on
the
height of
the wall
(Refer to
4 side
walls)
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
E≥20 E≥100
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥500 D≥500
E≥20 E≥100
F≥600 F≥500
A≥10 A≥50
B≥300 B≥100
C≥10 C≥50
D≥300 D≥100
E≥20 E≥100
F≥500 F≥500
A≥10
B≥300
A≥200
B≥300
E≥400
16
INSTALLATION SPACE
ENGLISH
INSTALLATION SPACE