OUTDOOR UNITS INFORMATION
9
ENGLISH
Power Supply : 380V, 60Hz / 380 – 415V, 50Hz
Model Name : ARUV***LLS4, ARUV***LLN4
CAUTION
* ARUV200LLN4 (Single Unit) model can guarantee the operation only within 160% combi-
nation ratio.
Notes :
1) We can guarantee the operation only within 130% combination ratio.
If you want to connect more than 130% combination ratio, please contact us and dis-
cuss the requirement.
2) In case that operating indoor units ratio to rated capacity of outdoor unit is more than
130%, the airflow should be operated as low step in the all indoor units.
3) In case of Space Saving Model (ARUV***LLN4), we can recommend the operation
within 120% combination ration for two or more combination.
4) The numbers in parentheses means maximum connectable indoor units in accordance
with outdoor units combination.
n Combination Ratio(50~200%)
Number of Outdoor units
Combination Ratio
Standard Model Space Saving Model
Single Unit
200% 160%*
Two Units Combination
160% 120%
Three or More Units Combination
130% 120%
!
n Standard Model
OUTDOOR UNITS INFORMATION
Unit
1 Outdoor Unit
System(HP)
Model
Combination Unit
Independent Unit
Refrigerant Precharged
Amount
kg
lbs
Number of maximum connectable indoor units
Net Weight
kg
lbs
Dimensions (WxHxD)
mm
inch
(36-7/32 × 66-5/32 ×
29-29/32) × 1
(36-7/32 × 66-5/32 ×
29-29/32) × 1
(36-7/32 × 66-5/32 ×
29-29/32) × 1
Piping Connections
mm(inch)
mm(inch)
10 12 14
ARUV100LLS4ARUV120LLS4ARUV140LLS4
ARUV100LLS4ARUV120LLS4ARUV140LLS4
5.0 5.0 5.0
11 11 11
16(25) 20(30) 23(35)
173 × 1 178 × 1 178 × 1
381 × 1 392 × 1 392 × 1
(920 × 1,680 × 760) × 1 (920 × 1,680 × 760) × 1 (920 × 1,680 × 760) × 1
9.52(3/8) 12.7(1/2) 12.7(1/2)
22.2(7/8) 28.58(1-1/8) 28.58(1-1/8)