Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using
duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Capacity 10~14 HP 16~22 HP
Max. RPM
Standard 730 950
op1 800 1000
op2 820 1000
op3 850 1000