72
ELECTRICAL WIRING
ENGLISH
Target pressure adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn8” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“op1” ~ “op6” Push the ‘●’ button
Target pressure is set
Select the Option using ‘▶’, ‘◀’ Button :
“HEAT” , “COOL” Push the ‘●’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
• “Heat” and “Condensing temperature variation” is not applied in ARUV***LLS4/LLN4.
!
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat” “Cool”
oFF Not setting
op1 Increase capacity Increase capacity
+2 °C -3 °C
op2
Decrease power consumption
Increase capacity
-2.5 °C -1.5 °C
op3
Decrease power consumption Decrease power consumption
-4.5 °C +2.5 °C
op4
Decrease power consumption Decrease power consumption
-6.5 °C +4.5 °C
op5
Decrease power consumption Decrease power consumption
-8.5 °C +6.5 °C
op6
Decrease power consumption Decrease power consumption
-10.5 °C +8.5 °C