The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correc-
tion Factor) value of indoor unit.
Additional charge(kg) = Total liquid pipe : Ø 25.4 mm x 0.480 (kg/m)
+ Total liquid pipe : Ø 22.2 mm x 0.354 (kg/m)
+ Total liquid pipe : Ø 19.05 mm x 0.266 (kg/m)
+ Total liquid pipe : Ø 15.88 mm x 0.173 (kg/m)
+ Total liquid pipe : Ø 12.7 mm x 0.118 (kg/m)
+ Total liquid pipe : Ø 9.52 mm x 0.061 (kg/m)
+ Total liquid pipe : Ø 6.35 mm x 0.022 (kg/m)
+ CF value of indoor unit
Amount refrigerant of Indoor units
Example) 4Way Ceiling Cassette 14.5 kW -1ea, Ceiling concealed Duct 7.3 kW-2ea,
Wall Mounted 2.3 kW-4ea
CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
Attach the additional refrigerant table of IDU.
CAUTION
Do not use 0 or 1 series of indoor unit. ex)ARNU****0(X) , ARNU****1(X)
!