PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
27
ENGLISH
- Pipe connections can be done on the front side or on the side according to the installation 
- Be sure to let 0.2kgf/cm
2
Nitrogen flow in the pipe when welding.
- If Nitrogen was not flown during welding, many oxidized membranes may form inside the pipe
and disturb the normal operations of valves and condensers.
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
- Align the center of the piping and sufficiently tighten the flare nut by hand. 
- Tighten the flare nut with torque wrench until the wrench clicks.
PIPE CONNECTIONS BETWEEN INDOOR AND
OUTDOOR UNIT