ZRUM200LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXB
Combination Unit (1) - ZRUM200LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 28.65 - 27.22 - 26.24
Running Current by Voltage (Heating,Rated) A 20.66 - 19.62 - 18.91
Cooling Capacity Rated
kW 56.0
Btu/h 191,100
Heating Capacity
Rated
kW 56.0
Btu/h 191,100
Max
kW 63.0
Btu/h 215,000
Power Input(Cooling) Rated kW 17.54
Power Input(Heating) Rated kW 12.64
Efficiency
EER(Rated) W/W 3.19
COP(Rated) W/W 4.43
SEER Wh/Wh 8.42
SCOP Wh/Wh 5.13
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 320
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 900 x 2
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1 x 2
Number of Revolution rev./min 3,600 x 2
Motor Output W x No. 5,300 x 2
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 1,240 x 1,745 x 760
Shipping(W x H x D) mm 1,282 x 1,919 x 802
Weight
Net kg 300
Shipping kg 310
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-13