ZRUM260LTE6
63 125 250 500 1000 2000 4000 8000 Overall [dB(A)]
98.8 85.7 82.9 81.7 77.6 73.0 70.9 64.0 83.5
99.6 87.0 83.8 82.8 78.7 74.0 71.1 64.3 84.5
Octave Band [Hz]
Cooling [dB]
Heating [dB]
10
20
30
40
50
60
70
80
90
100
110
120
63 125 250 500 1000 2000 4000 8000
Sound Power Level (0dB = 10E-6μW/m
2
)
Octave Band Center Frequency (Hz)
NR-70
NR-65
NR-60
NR-55
NR-50
NR-45
NR-40
NR-35
NR-30
NR-75
NR-25
NR-20
NR-80
NR-85
NR-90
Cooling
Heating
NR-95
NR-100
NR-105
NR-110
Sound level [ dB(A), @ Standard condition ]
Cooling / Heating 83.5 / 84.5
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference acoustic intensity 0dB = 10E-6μW/m2
■ Refer to the Model Specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions are
different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment in
installed.
Multi V i
10. Sound Levels
Product Data
10-21

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V ZRUM080LTE6 and is the answer not in the manual?

LG Multi V ZRUM080LTE6 Specifications

General IconGeneral
BrandLG
ModelMulti V ZRUM080LTE6
CategoryHeat Pump
LanguageEnglish

Related product manuals