1.2 Installation Flow Chart
YES
NO
NO
A
min
= Minimum installation required area
m
c
= Total amount of refrigerant in the system (kg)
LFL(Lower Flammability Limit)(kg/m³) = 0.307 kg/m³
h
0
: The Vertical Distance from the floor to the point of Release (m)
m
c
15.964 kg
Installation
m
c
30 kg
YES
Is the area ?desitas nimA fo
NO
YES
YES
Is the area ?desitas nimA fo
NO
Unable to install
A
min
= (m / (2.5 x (LFL)
(5/4)
x h
o
))
2
not less than A
min
= m
c
/ (0.75 x LFL x h
o
)
refer to natural ventilation
chapter.
*
Installation by adding
natural ventilation
A
min
= (m
c
/ (2.5 x (LFL)
(5/4)
x h
o
))
2
not less than A
min
= m
c
/(0.75 x LFL x h
o
)
c
Installation of Outdoor Unit
1. Information for Refrigerant
Installation
2