EasyManua.ls Logo

LG MultiSITE CRC2 Series - TECHNICAL SPECIFICATIONS AND COMPLIANCE; Product and Sensor Performance Details

LG MultiSITE CRC2 Series
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
SPECIFICATIONS
PREMTBVC2, PREMTBVC3, and PREMTBVC4
Dimensions
• Height: 4.72 in
• Width: 3.39 in
• Depth: 1.06 in
Power Requirements
• 12 VDC, 2.34W, supplied by IDU
Operating Conditions
• 32 °F - 122 °F
• 0% - 95% R.H. non-condensing
Storage Conditions
• -22 °F - 122 °F
• 0% - 95% R.H. non-condensing
Temperature Sensor
• Local 10 K NTC type 2 thermistor
Temperature Sensor Resolution
• ± 0.2 °F
Temperature Control Accuracy
• ± 0.9 °F @ 70 °F, typical calibrated
Humidity Sensor and Calibration
• Single point calibrated bulk polymer type sensor
Humidity Sensor Precision
• Reading range from 10-90 % R.H. non-condensing,
10 to 20% precision: 10%
20% to 80% precision: 5%
80% to 90% precision: 10%
Humidity Sensor Stability
• Less than 1.0 % yearly (typical drift)
Dehumidification Setpoint Range
• 30% - 95% R.H.
Occ, Stand-By and Unocc Cooling Dual Setpoint Range
• 52 - 99 °F
Occ, Stand-By and Unocc Heating Setpoint Range
• 40 °F - 90 °F