Trouble Shooting Guide
- 66 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
41
47
44
45
46
65
D-pipe sensor (Inv)
D-pipe sensor (Cons)
Air sensor
Condenser Pipe sensor
Suction Pipe sensor
Heat sink
sensor
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
•
Connector connection error
• Faulty PCB
•
Faulty sensor (Open / Short)
• Normal resistor : 200 kΩ/ at 25 ˚C (Unplugged)
• Normal voltage : 4.5 V DC / at 25 ˚C (plugged)
• Refer to sensor resistance table.
• Normal resistor : 10 kΩ/ at 25 ˚C (Unplugged)
• Normal voltage : 2.5V DC / at 25 ˚C (plugged)
• Refer to sensor resistance table.
• Normal resistor : 5 kΩ/ at 25 ˚C (Unplugged)
• Normal voltage : 2.5 V DC / at 25 ˚C (plugged)
• Refer to sensor resistance table.
• Normal resistor : 5 kΩ/ at 25 ˚C (Unplugged)
• Normal voltage : 2.5 V DC / at 25 ˚C (plugged)
• Refer to sensor resistance table.
Display
code
Title Cause of error Check point & Normal condition
of each sensor.
Repair or Change the PCB.
of each sensor.