of each sensor.
Repair or Change the PCB.
of each sensor.
61
62
Condenser
pipe sensor
temp. high
Heat sink sensor
temp. high
• condenser pipe
sensor detected high
temp. (65 ˚C)
• heat sink sensor
detected high temp.
(85 ˚C)
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
• Normal resistor : 5 kΩ at 25 °C (Unplugged)
• Normal voltage : 2.5 V DC at 25 °C (Plugged)
• Check the load condition.
• Check the sensor of heat sink.
• Normal resistor : 10 kΩ at 25 °C (Unplugged)
• Normal voltage : 2.5 V DC at 25 °C (Plugged)
Display
code
Title Cause of error Check point & Normal condition