- 73 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Trouble Shooting Guide
Check of compressor
Comp
Copper
pipe
V
U
W
Comp
Ω
Ω
n Check resistance of the compressor n Check Insulation resistance of the compressor
Model
Resistance ( ) at 20 °C
U-V U-W V-W
AHBW166A0 0.520 0.516 0.513
AHBW146A0 0.520 0.516 0.513
AHBW126A0 0.520 0.516 0.513
Resistance ( ) at 20 ℃
Terminal All models
U-GND
More than 2M
V-GND
More than 2M
W-GND
More than 2M
Model
Resistance ( ) at 25 °C
U-V U-W V-W
AHBW168A0 1.183 1.174 1.181
AHBW148A0 1.183 1.174 1.181
AHBW128A0 1.183 1.174 1.181
Resistance ( ) at 25 ℃
Terminal All models
U-GND
More than 2M
V-GND
More than 2M
W-GND
More than 2M
Model
Resistance ( ) at 20 °C
U-V U-W V-W
AHBW096A0 0.997 0.980 0.965
AHBW076A0 0.997 0.980 0.965
AHBW056A0 0.997 0.980 0.965
Resistance ( ) at 20 ℃
Terminal All models
U-GND
More than 2M
V-GND
More than 2M
W-GND
More than 2M

Related product manuals