Code Item Detail Remark
Note Starting date (Sunday:1,Monday:2, ···· ,Saturday:7)
Default 06
Range 01 ~ 07
Value #2
Value #1
Note Starting time in 24 hours(00 ~ 23)
Default 23
Range 00 ~ 23
27 Function Setting pasteurisation Operation
Description Setting pasteurisation temperature
Value #1 Note Maximum heating temperature
Default 70 °C
Range 40 ~ 80 °C
Value #2 Note Maximum heating duration in minute
Default 10 min
Range 05 ~ 60 min
28 Function Setting control parameter for Domestic hot water heating operation
Description See below notes for each values
Value #1 Note Temperature gap from Value #2 of Function Code 28
Default 05 °C
Range 01 ~ 20 °C
Value #2 Note
Maximum temperature generated by AWHP compressor cycle
Default 48 °C
Range 40 ~ 48 °C
29 Function Setting control parameter for Domestic hot water heating operation
Description See below notes for each values
Value #1
Note Temperature gap from target Domestic hotwater temperature.
(This value is required to frequent ON and OFF of water tank heater.)
Default 03 °C
Range 02 ~ 04 °C
Value #2
Note
Determining heating demand priority between Domestic hot water tank
heating and under floor heating
Default 00 : Sanitary water tank priority
Range 01 : under floor heating
Only available
when Domestic
hot Water
Tank is installed.
• To use
disinfection mode,
Domestic hot water
heating should be
enable.
25
Function
Setting Heating flow temperature range for weather-dependent operation
Description Setting Heating flow max / min temperature for
weather-dependent operation
Value #1 Note Upper limit of setting range
Default 57 °C
Range 35 ~ 57 °C
Value #2 Note Lower limit of setting range
Default 15 °C (*20 °C)
Range 15 ~ 34 °C (*20 ~ 34 °C)
26 Function Setting pasteurisation operation
Description Setting start/maintain time for pasteurisation
Value #1 Note
Enable / Disable of pasteurisation operation(00:Disable , 01:Enable)
Default 00
Range 00 ~ 01
Domestic hot water
* : Electric heater
is not used.
heating should be
enable.
• If Domestic hot
water heating is
disable, the disinf-
ectionmode will not
beoperated although
Value #1 of Code26
is set as '01'.
System Set-Up
82 Air-to-Water Heat Pump