Page #10 background image
- 10 -
Outdoor
Outdoor Units
AHUW146A2
AHUW096A3
Combination Indoor Units
AHNW16606B0
AHNW16606B0
Power Supply
Ø / V / Hz
1/220-240/50
1 / 220-240 / 50
Maximum Running
Cooling
A
25
19
Current
Heating
A
25
19
Wiring Connections
For Power Supply
(Included Earth)
Number of wires
3
3
* Capacity
Cooling(Under floor)
kW
11.0
Heating(Under floor)
kW
14.0
* Power Input
Cooling(Under floor)
kW
3.04
Heating(Under floor)
kW
3.16
*EER
Cooling(Under floor)
W/W
3.61
*COP
Heating(Under floor)
W/W
4.44
Operation Range (Min.~Max.)
Outdoor Temperature
Cooling
°C DB
5 ~ 48
Heating
°C DB
-20 ~ 30
Compressor
Type
-
Hermetic Motor
Model
-
GPT442MBA
Quantity
EA
1
Displacement
cm
3
/Rev.
44.2
Capacity
kW
13.92
Compressor Motor
Type
-
Brushless
Quantity
EA
1
Rated Output
W
4,000
Refrigerant
Type
-
R410A
Charge
g
2,300
Control
-
Electronic Expansion Valve
Refrigerant Oil
Type
-
FVC68D
Charged Volume
cc
1,300
Heat Exchanger
Quantity
EA
2
Rows
EA
2
Columns
EA
32
FPI
Fins/inch
14
Fan
Type
-
Propeller
Quantity
EA
2
Air Flow Rate
CMM(l/s)
55
Fan Motor
Model
-
BLDC
Quantity
EA
2
Output
W
124
Sound Power Level
Heating
dB
69
Liquid Piping Connection
Type
-
Flare
Outer Diameter
mm(inch)
Ø 9.52 (3/8)
Gas Piping Connection
Type
-
Flare
Outer Diameter
mm(inch)
Ø 15.88 (5/8)
Piping Length (Outdoor Unit ~
Indoor Unit)
Minimum
m
3
Standard
m
7.5
Maximum
m
50
Height Difference (Outdoor
Unit ~ Indoor Unit)
Maximum
m
30 30
Additional Refrigerant Charge
g/m
40
Dimensions
Unit(W x H x D)
mm
950 x 1,380 x 330
Packed Unit(W x H x D)
mm
1,140 x 1,462 x 461
Weight
Unit
kg
94
Packed Unit
kg
107
**Rated water flow rate
LPM
40
9.0
9.0
2.88
2.23
3.12
4.04
5 ~ 48
-20 ~ 30
Hermetic Motor
GJT240MAA
1
24
7.41
Brushless
1
2,137
R410A
1,800
EEV
FVC68D
900
1
2
38
14
Propeller
1
58
BLDC
1
124
65
Flare
Ø 9.52 (3/8)
Flare
Ø 15.88 (5/8)
3
7.5
50
40
950 × 834 × 330
1,065 × 918 × 461
59
65
26
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. ** Indoor unit Rated water flow rate.