24
110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load
Low Line Loss Voltage + 10V
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min、110%~130%: 1min、>130% : 1sec
100%~110%: 30sec、110%~130%: 10sec、>130% : 1sec
≦ 3 % @ 100% Linear Load; ≦ 6 % @ 100% Non-linear Load
3 hours recover to 90% capacity
4 hours recover to 90% capacity
Depending on applications
UPS unit: 580X438X133
Battery pack: 580X438 X133
UPS unit: 668X438X133
Battery pack: 580X438 X133
UPS unit: 17
Battery pack: 57
UPS unit: 20
Battery pack: 63
0 ~ 40°C (the battery life will down when > 25°C)
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
** When using internal batteries from 16-19, the unit will de-rate according to the below formula: P = P
Rating
x (N/20 x 100%).
***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice.