6. Specifications
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
≧ 0.99 @ 220-230 VAC (input voltage)
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode)
100%~110%: audible warning
110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to
bypass mode when the utility is normal.
>130%: UPS shuts down immediately at battery mode or transfer to bypass
mode when the utility is normal.
≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
≦ 4 % THD (Linear Load)
≦ 7 % THD (Non-linear Load)
4 hours recover to 90% capacity (Typical)
20-90 % RH @ 0- 40°C (non-condensing)
Less than 45dBA @ 1 Meter
Supports Windows® 98/2000/2003/XP/Vista/2008, Windows® 7, Linux, and
MAC
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC