Service Menu Parameters
65
HIGH TEMP SENSOR A HTA W 0 - 9999 sec
LOW TEMP SENSOR A LTA W 0 - 9999 sec
HIGH HUM SENSOR A HHA W 0 - 9999 sec
LOW HUM SENSOR A LHA W 0 - 9999 sec
ENABLE - DISAB -- -
MAIN FAN OVERLOAD FOL W Disabled, Enabled
LOSS OF AIRFLOW LOA W Disabled, Enabled
CLOGGED FILTERS CF W Disabled, Enabled
HIGH ROOM TEMP HRT W Disabled, Enabled
LOW ROOM TEMP LRT W Disabled, Enabled
HIGH ROOM HUM HRH W Disabled, Enabled
LOW ROOM HUM LRH W Disabled, Enabled
HIGH TEMP SENSOR A HTA W Disabled, Enabled
LOW TEMP SENSOR A LTA W Disabled, Enabled
HIGH HUM SENSOR A HHA W Disabled, Enabled
LOW HUM SENSOR A LHA W Disabled, Enabled
TYPE -- -
MAIN FAN OVERLOAD FOL W MSG, WRN, ALM
LOSS OF AIRFLOW LOA W MSG, WRN, ALM
CLOGGED FILTERS CF W MSG, WRN, ALM
HIGH ROOM TEMP HRT W WRN
LOW ROOM TEMP LRT W WRN
HIGH ROOM HUM HRH W WRN
LOW ROOM HUM LRH W WRN
HIGH TEMP SENSOR A HTA W WRN
LOW TEMP SENSOR A LTA W WRN
HIGH HUM SENSOR A HHA W WRN
LOW HUM SENSOR A LHA W WRN
Page 4 of 7
PASSWORD -W -
DELAY -- -
COMP 1 OVERLOAD OL1 W internal
COMP 2 OVERLOAD OL2 W internal
COMP 1 HIGH PRESSURE HP1 W internal
COMP 2 HIGH PRESSURE HP2 W internal
COMP 1 LOW PRESSURE LP1 W internal
COMP 2 LOW PRESSURE LP2 W internal
COMP 1 PUMPDOWN FAIL PD1 W internal
COMP 2 PUMPDOWN FAIL PD2 W internal
DIG SCROLL1 HIGH TEMP HT1 W internal
DIG SCROLL2 HIGH TEMP HT2 W internal
EL HEAT HIGH TEMP EHO W 0 - 9999 sec
Table 28 Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
SET
ALARMS