Service Menu Parameters
63
Page 7of 7
Status Humidifier Problem HUM PROB R OK, Act
Status DT1 (Outdoor/Glycol) DT1 R OK, Act
Status DT2 (Glycol/Room) DT2 R OK, Act
Status DT3 (Room/Setpoint) DT3 R OK, Act
Status Min CW MIN CW R OK, Act
LWD Value LWD Val R Off, On
Status LSI LSI R Off, On
Table 28 Set alarms parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 7
Password PASSWORD W -
Return Sensor Alarms RTN SNSR W Disabled, Enabled
High Return Temperature HI TEMP W 34-210°F (1-99°C)
Low Return Temperature LO TEMP W 34-210°F (1-99°C)
High Return Humidity HI HUM W 1-99%
Low Return Humidity LOW HUM W 1-99%
Sensor A Alarms SENSOR A W Disabled, Enabled
High Temperature Sensor A HI TEMPA W 34-210°F (1-99°C)
Low Temperature Sensor A LO TEMPA W 34-210°F (1-99°C)
High Humidity Sensor A HI HUM A W 1-99%
Low Humidity Sensor A LO HUM A W 1-99%
Table 27 Diagnostics / service mode parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
SERVICE
SET
ALARMS