EasyManua.ls Logo

Liebert ICOM - Table 27 Diagnostics; Service Mode Parameters

Liebert ICOM
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Menu Parameters
61
Table 27 Diagnostics / service mode parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 7
Password PASSWORD W -
HP 1 Alarm Code HP1 CODE W 0-999
HP 2 Alarm Code HP2 CODE W 0-999
HT 1 Alarm Counter HT1 CNT W 0-999
HT 2 Alarm Counter HT2 CNT W 0-999
LP 1 Alarm Code LP 1 CODE W 0-999
LP 2 Alarm Code LP2 CODE W 0-999
Actual LP1 Pressure
LP1 ACT R - 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual LP2 Pressure
LP2 ACT R - 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual HP1 Pressure
HP1 ACT R - 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Actual HP2 Pressure
HP2 ACT R - 145.0 - 725.0 psi
(-10.0 to 50.0 bar)
Page 2 of 7
Password PASSWORD W -
Manual Mode MANUAL W No, Yes
Motor(s) MOTOR(S) W Off, On
Compressor 1 COMP1 W Off, On
Compressor 1 C1 MODE W Run, Evacuate, Charge
Compressor 1 Capacity C1 CAP W Off, On
Compressor 1 Cycle Ramp C1 CYCLE W 0-100%
Compressor 1 LLSV LLSV 1 W Off, On
Compressor 2 COMP2 W Off, On
Compressor 2 C2 MODE W Run, Evacuate, Charge
Compressor 2 Capacity C2 CAP W Off, On
Compressor 2 Cycle Ramp C2 CYCLE W 0-100%
Compressor 2 LLSV LLSV 2 W Off, On
Page 3 of 7
Password PASSWORD W -
Electric Heat 1 (or HG/HW) EL HEAT1 W Off, On
Electric Heat 2 (or E.Heat 1) EL HEAT2 W Off, On
Electric Heat 3 (or E.Heat 2) EL HEAT3 W Off, On
SCR Heat SCR HEAT W 0-100%
Dehumidification Output DEHUM W Off, On
Humidfier Fill HUM FILL W Off, On
Humidifier HUM W Off, On
Humidfier Drain H DRAIN W Off, On
Humidifier Current HUM.C. R 0.00 - 99.99A
Page 4 of 7
SERVICE

Table of Contents