Liebert ICOM - Table 30 System; Network Setup Parameters-Large Display Only

Liebert ICOM
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Menu Parameters
70
Freecool Sensor PTC or NTC FC SNSR W PTC, NTC
Freecool Sensor FC SNSR W ±18°F (±9.9°C)
Calibrated Freecool Sensor CAL FC R 4-113°F (-15 to 45°C)
Supply Sensor PTC or NTC SUP SNSR W PTC, NTC
Supply Sensor SUP TEMP W ±18°F (±9.9°C)
Calibrated Supply Sensor CAL SUP R 32-122°F (0-50°C)
Temperature Sensor C TEMP C W ±18°F (±9.9°C)
Calibrated Temperature Sensor C CAL C R 32-122°F (0-50°C)
Humidity Sensor C HUM C W ±9.9%
Calibrated Humidity Sensor C CAL C R 20-80%
Table 30 System / network setup parameters—large display only
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 2
Password PASSWORD W -
Number of Connected
Units
W1-32
Teamwork Mode W No, 1, 2
Configuration Safe
R
Not Available, Invalid, OK,
Changed, Updating
Configuration Safe W No, SaveLoad
Network Safe
R
Not Available, Invalid, OK,
Changed, Updating
Network Safe W No, Save, Load
SW Version W
Page 2 of 2
Password PASSWORD W -
IP Address W IP Range
Table 29 Sensor calibration / setup parameters