23
Battery Run Times
Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
AGENCY
Safety UL 1778, c-UL Listed
Surge
ANSI C62.41, Category A, Level 3
(IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria A
ESD EN61000-4-2, Level 3, Criteria A
Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient/Burst
EN61000-4-4, Level 4, Criteria A
Emissions FCC Part 15, Subpart B, Class B
Conducted Immunity EN61000-4-6, Level 3, Criteria A
Harmonics EN61000-3-2
Flicker EN61000-3-3
Transportation ISTA Procedure 1A
Load % 350VA 500VA 650VA
5 319 156 192
10 146 113 95
20 75 49 42
30 45 31 30
40 35 22 21
50 24 17 14
60 20 11 13
70 17 9 10
80 13 7 7
90 10 5 6
100 9 4 5