Operation
Set setpoints
KeepSdepressed for 3 seconds. Display , and temperature setpoint (“t” + “setpoint”).
PressSto switch between temperature set status and humidity set status (“H” + “setpoint”).
Pressorto set the setpoint (keeping depressed could fast set).
KeepSdepressed for 3 seconds to save the settings, and exit.
The setting status will exit if there is no key operation for 30 seconds, and the settings will not be saved.
Factory setpoints are 38.0 and 60.0%RH.
Parameter code table
Code
Range
Remark
Factory
set
U10
U11 ~ 99.9
99.9
U11
-40.0~ U10
-40.0
U12
0.1 ~ 10.0
Relative value, real value = setpoint + U12
0.3
U13
0.1 ~ 10.0
Relative value, real value = setpoint + U13
0.1
U14
0.0 ~ 99.9
Relative value, real value = setpoint U14
35.0
U15
2.0 ~ 99.9
Relative value, real value = setpoint + U15
99.9
U16
0.0 ~ 20.0
Effective when U73 = 1
0.2
U30
-20.0 ~ 20.0
0.0
U40
0 ~ 2
0: sec, 1: min., 2: hour
0
U41
1 ~ 999
120
U42
0 ~ 2
0: sec, 1: min., 2: hour
1
U43
1 ~ 999
120
U46
0 ~ 3
0: Timer output
1: High temperature/humidity protection
2: Timer output + High temp./humi. protection
3: Disable
2
U47
0 ~ 1
0: R1/R2 keep working during auto tuning
1: R1/R2 keep off during auto tuning
1
U50
0.1 ~ 20%RH
2.0
U51
2 ~ 300 sec.
5
U52
-20.0 ~ 20.0%RH
0.0
U53
1.0 ~ 20.0%RH
Relative value, real value = setpoint + U53
5.0
U54
0.0 ~ 20.0%RH
Relative value, real value = setpoint + U54
0.0
U55
0.0 ~ 99.9%RH
Relative value, real value = setpoint U55
0.0: disable the alarm function
20.0
U56
0.0 ~ 99.9%RH
Relative value, real value = setpoint + U56
0.0: disable the alarm function
30.0
U60
0 ~ 999
0: do not counter the times of egg turn
0
U61
0 ~ 2
0: sec, 1: min., 2: hour
1
U62
1 ~ 999
90
U63
0 ~ 2
0: sec, 1: min., 2: hour
1
U64
1 ~ 999
90
U66
0 ~ 1
0: reset, 1: not reset (keeps)
0
U67
0 ~ 1
0: not save, 1: save
0
U68
0 ~ 1
0: reset, 1: not reset (keeps)
1
U69
0 ~ 999 day
0: do not counter the days of incubation
30
U70
0 ~ 2
0: disable, 1: alarm if short 2: alarm if open
0
U71
0 ~ 1
0: disable, 1: enable
1
U73
0 ~ 1
0: PID, 1: on/off control
0
U74
10 ~ 100%
Percent of heater’s whole power rate
50
P
0.1 ~ 9999
2.6
I
0 ~ 9999
500
d
0 ~ 9999
50
U99
000 ~ 999
000: disable password
000