FireSystemPro Damper unit
Connect re damper to damper unit
One fire damper per Pro-S is allowed. The damper is controlled by either an actuator with spring return, a 3-point actuator or
a 0-10 V VAV actuator. When an actuator is used, end position switches must be added to terminals S1/S4, S2 and S6.
Connect smoke detector to damper unit
One smoke detector per PRO-S is allowed. Remove the 2.2 kΩ resistor from the damper unit and move it to the smoke
detector. The digital output DO1 works as a +19 V DC power supply for the smoke detector. AI1 is used to read the detector
status in the range 0-100mA, and is short circuit proof.
Wiring alternatives
Temperature sensors and resistors can be added to the damper unit according to the wiring diagram 3. The 1 kΩ resistor is
removed when a temperature sensor or the VAV signal 0-10 from zone is connected.
Wiring diagram 1: Actuators and end position switches
Wiring diagram 2: Smoke detector connected to power and Analogue input 1
Wiring diagram 3: Wiring alternatives