Connecting Readers, Inputs, Outputs, and Temperature Sensors
233190 X3 Linear LLC 22 May 2013
13. If the output device is AC powered and normally energized, use the circuit
shown in the following diagram.
Connecting Outputs
CAUTION: Make sure all power is off before connecting outputs to blades.
Outputs can be connected either to an access control blade or to an output blade.
Access control blades have four, 3-pin output connectors mounted on the blade
as shown in Figure 18, dry contacts rated at 24V/2A.
Figure 18. Output connectors mounted on the access control blade.
Note: Output positions on the access control blade are output numbers 1, 2, 3,
and 4.
If more outputs are required beyond the four provided on the access control
blade, additional access control blades or output blades can be installed in the
node cabinet. For instructions, see Installing Additional Blades on page 9.
Output blades have eight male, 3-pin output connectors mounted on the blade, as
shown in Figure 19. Outputs support any output devices that operate on the
following maximum electrical ratings: 24V/2A.