Connecting Readers, Inputs, Outputs, and Temperature Sensors
233190 X3 Linear LLC 24 May 2013
Note: Steps 1-4 apply only to cabinets containing both a Mini-ITX
Network Controller board and a Network Node blade. Expansion
Node cabinets simply require that you remove power before
connecting any temperature sensor.
5. The cable lead from the white temperature sensor wire must connect to pin
one, and the cable lead from the black temperature sensor wire must connect
to pin two, of the temperature input connector. See the following diagram.
Note: For distances up to 500 feet (152.4 meters), use Category 3 cable.
For distances over 500 feet up to 1000 feet (304.8 meters), use
Category 5 cable.
6. Be sure that you are grounded.
7. Pull the cable through a knockout in the cabinet. Connect the 2-pin
temperature input connector to the temperature blade.
Black wire to pin 2
White wire to pin 1
2-pin
temperature
inputs
1
2
3
4
5
6
7
8
Pin 1
Pin 2