40 
 
  Chapter 6│Parameters 
6.1 Group A, Initialization 
Sets the initial parameters (group A parameter) such as Access Level Selection, password and 
etc.   
A1  Initialization 
  A1- 00  Retain   
  A1- 01  Access Level Selection   
Selects access level (edit/ view) 
0 : View Only 
Access to only parameter A1-01 
1 : User-Defined Parameter Access 
Access to only parameter A1-01 and A2-00 to A2-31   
2 : All Parameter Access 
All parameters can be edited and viewed 
 
Note: 
·  Once the password is set to A1-05, user cannot edit A1-01, A1-03, A2-01 to A2-32 before entering the correct 
password in A1-04. 
·  Once  E1-□□=  60  (Program  Lockout)  is  set,  user  cannot  edit  any  parameters  before  closing  the  assigned 
terminal, even when A1-01 = 1 or 2. 
·  When using Modbus communication to edit parameters, it is not possible to edit parameters via keypad until 
an ENTER command is given to the drive from the communication. 
·   
  A1- 02  Control Method Selection