45 
 
6.2 Group b, Application 
b1: Operation Mode Selection 
  b1- 00  Frequency Command Selection 1     
Selects the frequency command source for the REMOTE mode.   
Note:   
  When the run command is input with 0 Hz frequency command or below the minimum frequency, the RUN 
LED will blink.   
   
Frequency Command Selection 1     
0 : Keypad 
Allows two ways to input the frequency command.     
  Switching between the multi-step speed command in parameters L1-□□ (by digital input 
terminal). 
  Entering the frequency command on the keypad.   
1 : Control Circuit Terminal (Analog Input) 
Allows a voltage or current input as analog frequency command from terminal A1.   
□  Voltage Input 
Allows a voltage signal input via terminals A1. Refer to Table 6.4 for parameter settings.   
 
Table 6.4 Frequency Command Using Voltage Signals 
E3-01 = 0 
(Main Frequency Command) 
Ensure DIP switch A1 is 
placed to V (voltage)